BPE 20kVA/20kW MFII Series Online UPS 3‐Phase Input, 1‐Phase Output, External Battery Tower UPS

BPE
SKU:
MFII1120L32

Pricing available upon request

Current Stock:

High-performance True Online Double Conversion UPS with DSP-controlled pure sine wave output, IGBT-based inverter/rectifier, wide voltage & frequency range, ECO mode, battery optimization (16–20 units), generator compatibility, and optional parallel operation up to 4 units.

Key Features

  • True Online Double Conversion with DSP Controlled Pure Sine Wave Design
  •  IGBT based both Inverter & Rectifier
  •  Input Current Harmonic: ≤ 3%
  •  Optimization Battery Group, The Quantity of Battery: 16/18/20 Nos.
  •  High Input Power Factor 0.99 w High Output Power Factor 1.0
  •  Wide Input Voltage Range
  •  Wide Input Frequency Range (50Hz: 45~55Hz / 60Hz: 54~66Hz)
  •  Generator Compatibility & Phase Reversal Protection
  •  Support Economic Operation (ECO) Mode
  •  Self-Testing while UPS Startup
  •  Optional Parallel up to 4 units
  •  Static Bypass and Cold Start  Support 3/1 & 1/1 Operation

Technical Specifications

  • Capacity: 20 kVA
  • Input
    • Nominal Voltage: 380V / 400V / 415V AC (3P+N+PE)
    • Operating Voltage Range: 320V~480V AC Load Dependent
    • Operating Frequency Range: 50 / 60 Hz ± 10% (Auto Sensing)
    • Power Factor: ≥0.99
    • Bypass Voltage: -40% ~ +15% (Configurable)
    • Bypass Frequency: ±5% (Configurable)
    • ECO Range: Same as the Bypass, can be configured
    • Generator Input: Compatible
  • Output
    • Rated Voltage: 220V / 230V / 240V AC L+N+PE (Configurable)
    • Power Factor: 1.0
    • Voltage Regulation: ±1%
    • Frequency: Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.5 Hz Battery Mode
    • Crest Factor: 3:1
    • Overload: ≤105% for Continuous, ≤125% for 10 Min, ≤150% for 60 Sec, ≥150% for 200ms
    • Harmonic Distortion (THDv): ≤1%
    • Efficiency: 94.0% Dual Conversion Mode, 99.0% ECO Mode
  • Battery
    • Battery Voltage: 192V DC / 216V & 240V DC (Configurable)
    • Typical Recharge Time: 4-5 Hours to 90% of full Capacity
    • Charge Current: 18A
  • System Features
    • IP Protection: IP20
    • Transfer Time: Zero
    • EPO / ECO / CVCF: Shutdown UPS Immediately / ECO and CVCF Mode can be Configurable
    • Alarm / Protection: Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low
    • LED Display: Line Mode, Backup Mode, ECO Mode, Bypass Mode, Battery Low, Overload & UPS Fault
    • LCD Display: Input Voltage, Input Frequency, Output Voltage, Frequency, Current; Load Percentage, Battery Voltage, Charging/Discharging/Current Temperature & Remaining Battery Backup Time, Load VA/W, Load and Battery Barograph
  • Environmental
    • Temperature:
      • Operating: 0~50°C*
      • Storage: -15ºC ~ 60ºC
    • Humidity / Altitude: 0~95% RH Non-condensing / <1500 M
    • Noise: <58dBA
  • Physical
    • Dimension WxDxH (mm): 250 x 580 x 655
    • Net Weight (Kg): 38
  • Standards
    • Quality: ISO 90001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS, FCC
    • Safety: IEC/EN62040-1; Conformity to IEC / EN
    • EMC / Performance: IEC/EN62040-2 ; IEC/EN62040-3, Complying to CE, Compliance to UL
  • Communication Interface
    • Standard: RS-232
    • Optional: SNMP / ModBus / Dry Contact / USB / RS-485 / SMS Alert Card
    • Monitoring Software: NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000